首页  科学研究  学术论文  2009年
 
Ji J, Zhong W, Huo R, Sun JH, Asme (2009) (Amer Soc Mechanical Engineers: New York) 193-199
文章来源:WOS    作者:SKLFS    发布时间:2011-08-16

Ji J, Zhong W, Huo R, Sun JH, Asme (2009) 'CRITICAL CONDITIONS FOR FIRE-INDUCED SMOKE CONFINEMENT BY AIR CURTAIN IN LONG CHANNELS.' (Amer Soc Mechanical Engineers: New York) 193-199

Web link:

Keywords:

air curtain; long channel; smoke; Realizable k - epsilon model;

Abstract: The air curtain can be adopted to slow down or stop smoke spread, in case of channel fires, with no influence of the normal usage of the channels and on the human evacuation. The flow field of air curtain jet from ceiling to floor was divided into 3 sections, i.e. the section of impinging mixing, non-isothermal jet and impinging floor and the theoretical analysis of fire-induced smoke control by air curtain in long channels was carried out. The formulas of the critical conditions for absolutely preventing smoke from intruding the protected side were obtained. With the Realizable k - epsilon model and the numerical solutions of the formulas as the initial and boundary conditions, an application example was simulated. Results showed that the three-section analysis method was reasonable and the simulated results verified the rationality of the theoretical prediction model.

 
 
相关链接
Ji J, Zhong W, Huo R, Sun JH, Asme (2009) (Amer Soc Mechanical Engineers: New York) 193-199
联系我们
安徽省合肥市金寨路96号
中国科学技术大学
火灾科学国家重点实验室
邮政编码:230026
   
Tel:(+86)551 63601651
Fax:(+86)551 63601669
E-mail:sklfs@ustc.edu.cn
Copyright © 1990-2011 State Key Laboratory of Fire Science, University of Science and Technology of China
火灾科学国家重点实验室 版权所有 皖ICP备:002106505 号