Cheng XD, Bystrom A, Wickstrom U, Veljkovic M (2012) Thermal analysis of a pool fire test in a steel container. Journal Of Fire Sciences 30(2), 170-184. [In English]
Web link: http://dx.doi.org/10.1177/0734904111432834
Keywords: Thermal analysis; adiabatic surface temperature; pool fire; FDS; combustion characteristics; ventilation, tunnel
Abstract: A pool fire test was conducted in an uninsulated steel container under low ambient temperature condition, at -20 degrees C. The heat balance of the enclosure fire was analyzed. The size of the container was 12 mx 2.4 m and 2.4 m high, and it was made of 3-mm-thick steel. During the fire test, the fuel mass loss rate was recorded and the temperatures at different positions were measured with high-temperature thermocouples and plate thermometers. The fire scenario was simulated by using fire dynamics simulator software, and the simulated and measured results were compared. The coarse high-temperature thermocouple responded slower, and therefore, temperature measured by the high-temperature thermocouple was corrected to eliminate the effect of the thermal inertia. Furthermore, a simple two-zone model was proposed for estimating gas temperature in the enclosure of the highly conductive steel walls assuming a constant combustion rate. The convective and radiative heat transfer resistances at the inside and outside surfaces of the enclosure were analyzed.
 
 
相关链接
Cheng XD, Bystrom A, Wickstrom U, Veljkovic M (2012) Journal Of Fire Sciences 30(2), 170-184.
联系我们
安徽省合肥市金寨路96号
中国科学技术大学
火灾科学国家重点实验室
邮政编码:230026
   
Tel:(+86)551 63601651
Fax:(+86)551 63601669
E-mail:sklfs@ustc.edu.cn
Copyright © 1990-2011 State Key Laboratory of Fire Science, University of Science and Technology of China
火灾科学国家重点实验室 版权所有 皖ICP备:002106505 号